Duct Mounting Air Quality Sensor, Selectable Output 0/10Vdc or 4-20mA
KLQ
£294.00
Description
The self-calibrating microprocessor-controlled duct air quality sensor is used to determine the air quality on basis of a mixed gas sensor ⁄ VOC sensor.
It is used to measure the air quality for quantitative evaluation of room air pollution with contaminating gases.
The air quality sensor does not trace concentrations of individual gases, but assesses the mixed gas concentration.
Detectable gases: mixed gas, vapours of VOCs, cigarette smoke, automobile exhaust gases, human exhalation, combustion smoke (from wood, paper, plastics).
The sensor‘s lifetime depends on the type of burden and gas concentration.
Specification
Power Supply: 24V AC / DC (± 10%)
Power Consumption: < 1.5W / 24V DC typical
< 2.9VA / 24V AC typical
Peak Current 200mA
Sensor: VOC sensor (metal oxide), with automatic
self-calibration (VOC = volatile organic
compounds)
Measuring Range: 0…100% air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensibility low, medium, high
Output: 0 – 10V (OV = clean air, 10V = contaminated air) or
4…20mA (selectable via DIP switches; switch point
adjustable from 0…100% of output signal).
Measuring Accuracy: ± 20% of final value (referred to calibrating gas)
Service Life: > 60 months
Gas Exchange: By diffusion
Warm-up Time: Approx. 1 hour
Ambient Temperature: -10…+60˚C
Response Time: Approx. 1 minute, minimum flow rate 0.2 – 0.5m/s
Electrical Connection: 0.14 – 1.5mm², via terminals
Enclosure: Plastic, material polyamide, 30% glass-globe-
reinforced, with quick-locking screws
(slotted / Phillips head combination),
colour traffic white (similar to RAL 9016)
Enclosure Dimensions: 72 x 64 x 37.8mm (Tyr 1 without display)
Cable Gland: M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4mm
Protective Tube: Pleuroform™, material polyamide (PA6),
with torsion protection, Ø 20mm, NL = 202.5mm
Vmax = 30m/s (air)
Process Connection: By mounting flange, plastic (included in the
scope of delivery)
Protection Class: III (according to EN 60730)
Protection Type: IP 65 (according to EN 60529)
Standards: CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014 /
30 / EU
Weight | 30 g |
---|