Inside Light Sensor Multi-Ranging Lux 4-20mA Output
RHKF-I
£126.00
Description
These light intensity sensors measures the light level and are used to control luminaries, lighting systems, Venetian blinds and canvas blinds, etc. Applications in monitoring lighting conditions at workplaces, in greenhouses, storage halls, workshops and corridors, in outdoor areas, in industrial halls, in offices, in residential and business facilities. It is used for daylight-dependant constant light control, as light intensity or twilight sensor and to control sunshade equipment avoiding unnecessary heating-up of rooms.
Specification
Power Supply: 24V AC (± 20%); 15…36V DC for U variant
15…36V DC for I variant,
Depending on working resistance, residual ripple
stabilised ± 0.3V
Power Consumption: < 1W at 24V DC; < 2VA at 24V AC
Sensor: Light sensor with diffuser
Measuring Ranges: Multi-range switching (via DIP switches) with 4
switchable measuring ranges
0…500 Lux / 1 kLux / 5 kLux / 20 kLux
(other individual ranges optional e.g. 100 kLux)
Output: 4…20mA or 0 – 10V (2- or 3-wire connection)
Measuring Error: < 5% of final value
Ambient Temperature: 0…+50˚C
Electrical Connection: 0.14 – 1.5mm², via terminal screws on circuit board
Enclosure: Plastic, material ABS, colour pure white
(similar to RAL 9010)
Dimensions: 85 x 85 x 27mm (Baldur 1)
Installation: Wall mounting or in-wall flush box, Ø55mm,
base with 4-hole for mounting on vertically or
horizontally installed in-wall flush boxes for cable
entry from the back, with predetermined breaking
point for on-wall cable entry from top/bottom in
case of plain on-wall installation.
Protection Class: III
Protection Type: IP30
Standards: CE conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 / 30
/ EU
Weight | 760 g |
---|